INDUSTRIAL ATEX TRANSFORMER

THE ATEX TRANSFORMERS ARE CE MARKED TO THE ATEX DIRECTIVE FOR SAFE USE IN ZONES 1 POTENTIALLY EXPLOSIVE GAS AND 21 DUST ATMOSPHERES, WHERE THE T CLASS AND AMBIENT TEMPERATURES PERMIT. WOLF TRANSFORMERS ARE BOTH ATEX AND IECEX CERTIFIED.

Models operating from 0.5KV, 1KV, 500KV and 230V or 110V to 24V and 230V to 110V, the transformers are intended for use with the range of temporary ambient and task lights and with ancillary equipment for maintenance tasks. The transformers have 400VA and 320VA dual power rating options allowing them to be safely used in a range of upper operating ambient temperatures depending on power usage.

As standard, Transformers are supplied with a 15 meter SY Braided Screen Cable input cable fitted with an ATX plug and with four ATX output sockets fitted to the enclosure. The Transformers are available with a stainless steel or GRP enclosure, sealed to IP66, enabling use in wet and dusty conditions. In addition, a stainless steel outer protective skid makes the unit stronger and easier to handle for temporary installations ensuring that it can withstand the harshest of environments.

All ATEX power distribution systems are robust and durable in their construction, compact and portable for easy handling and fully flexible to enable different configurations to be built to your specific hazardous area requirement.

Category:

Features & Benefits

  • ATEX approved for use in Zones 1 explosive gas and 21 dust atmospheres
  • IECEx certified
  • Robust and durable construction
  • Transportable and portable design
  • Wide range of voltages available – 230V or 110V to 24V and 230V to 110V
  • 400VA and 320VA power rating options
  • Fitted with 4 x ATX socket outlets
  • Supplied with 15m SY cable and ATX plug
  • CEAG, STAHL and Appleton plug options available
  • Power temporary ambient and task lighting and ancillary maintenance equipment
  • 110V versions available with CTE (Centre Tap Earth) option

Technical Specification

Product Description GRP Stainless Steel
110V:24V 230V:24V 230V:110V 110V:24V 230V:24V 230V:110V
Code For Output Power ≤ 400VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66For Output Power ≤ 320VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66
(-20°C ≤ Ta ≤ +50°C)
For Output Power ≤ 400VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66For Output Power ≤ 320VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66
(-20°C ≤ Ta ≤ +42°C)
Type of Protection ‘e’ increased safety, ‘d’ flameproof
Area of Classification (Gas) Zones 1 and 2, Gas groups IIA, IIB and IIC
Temperature Class (Gas) T3 T3
Area of Classification (Dust) Zones 21 and 22, Dust Groups IIIA, IIIB and IIIC
Max. Surface Temperature (Dust) T195°C T195°C
Ambient Temperature 400VA -20°C to +35°C
320VA -20°C to +50°C
400VA -20°C to +30°C
320VA -20°C to +42°C
Certificate ATEX – LCIE02ATEX6248X
IECEX – LCI 04.0016X
ATEX – LCIE02ATEX6118X IECEX – LCI 11.0008X
Enclosure Glass reinforced polyester (GRP) enclosure,
marine grade (316L) stainless steel skid
Marine grade (316L) stainless steel
enclosure and skid
Power 320 / 400VA 320 / 400VA
Volts In 110V ac +6% -10% 110V ac
+6% -10%
110V ac +6% -10% 110V ac
+6% -10%
Input Cable 15m SY cable 4mm² with ATX 110V / 230V 2P+E plug fitted as standard
Volts Out 24V 110V 24V 110V
Socket Arrangement & Configuration 4 output sockets, ATX 110V / 24V 2P+E as standard
2 sockets on each unit side
Dimensions 504 x 465 x 285mm (L x W x H) 512 x 562 x 260 mm (L x W x H)
Ingress Protection IP66
  • Dual marked GRP Transformer certified T3 with an ambient temperature range of -20°C to +50°C at 320VA power and with an ambient temperature range of -20°C to +35°C at 400VA power.
  • Dual marked SS Transformer certified T3 with an ambient temperature range of -20°C to +42°C at 320VA power and with an ambient temperature range of -20°C to +30°C at 400VA power.
  • CEAG, Stahl and Marechal plug options and longer SY input cable available on request.
  • Ships braided cable for offshore applications to BS6883 available on request.
  • Changes may be made to the above specification without notification, details are available on request.