Features & Benefits
- ATEX approved for use in Zones 1 explosive gas and 21 dust atmospheres
- IECEx certified
- Robust and durable construction
- Transportable and portable design
- Wide range of voltages available – 230V or 110V to 24V and 230V to 110V
- 400VA and 320VA power rating options
- Fitted with 4 x ATX socket outlets
- Supplied with 15m SY cable and ATX plug
- CEAG, STAHL and Appleton plug options available
- Power temporary ambient and task lighting and ancillary maintenance equipment
- 110V versions available with CTE (Centre Tap Earth) option
Technical Specification
Product Description | GRP | Stainless Steel | ||||
110V:24V | 230V:24V | 230V:110V | 110V:24V | 230V:24V | 230V:110V | |
Code | For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +50°C) |
For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +42°C) |
||||
Type of Protection | ‘e’ increased safety, ‘d’ flameproof | |||||
Area of Classification (Gas) | Zones 1 and 2, Gas groups IIA, IIB and IIC | |||||
Temperature Class (Gas) | T3 | T3 | ||||
Area of Classification (Dust) | Zones 21 and 22, Dust Groups IIIA, IIIB and IIIC | |||||
Max. Surface Temperature (Dust) | T195°C | T195°C | ||||
Ambient Temperature | 400VA -20°C to +35°C 320VA -20°C to +50°C |
400VA -20°C to +30°C 320VA -20°C to +42°C |
||||
Certificate | ATEX – LCIE02ATEX6248X IECEX – LCI 04.0016X |
ATEX – LCIE02ATEX6118X IECEX – LCI 11.0008X | ||||
Enclosure | Glass reinforced polyester (GRP) enclosure, marine grade (316L) stainless steel skid |
Marine grade (316L) stainless steel enclosure and skid |
||||
Power | 320 / 400VA | 320 / 400VA | ||||
Volts In | 110V ac +6% -10% | 110V ac +6% -10% |
110V ac +6% -10% | 110V ac +6% -10% |
||
Input Cable | 15m SY cable 4mm² with ATX 110V / 230V 2P+E plug fitted as standard | |||||
Volts Out | 24V | 110V | 24V | 110V | ||
Socket Arrangement & Configuration | 4 output sockets, ATX 110V / 24V 2P+E as standard | |||||
2 sockets on each unit side | ||||||
Dimensions | 504 x 465 x 285mm (L x W x H) | 512 x 562 x 260 mm (L x W x H) | ||||
Ingress Protection | IP66 |
- Dual marked GRP Transformer certified T3 with an ambient temperature range of -20°C to +50°C at 320VA power and with an ambient temperature range of -20°C to +35°C at 400VA power.
- Dual marked SS Transformer certified T3 with an ambient temperature range of -20°C to +42°C at 320VA power and with an ambient temperature range of -20°C to +30°C at 400VA power.
- CEAG, Stahl and Marechal plug options and longer SY input cable available on request.
- Ships braided cable for offshore applications to BS6883 available on request.
- Changes may be made to the above specification without notification, details are available on request.